@lexi_abreu: #greenscreenvideo @FullSttopp I hope this answers your question! #electricalquestions
LextheElectrician
Open In TikTok:
Region: US
Friday 04 November 2022 00:40:47 GMT
67796
2984
109
13
Music
Download
No Watermark .mp4 (
9.42MB
)
No Watermark(HD) .mp4 (
9.42MB
)
Watermark .mp4 (
0MB
)
Music .mp3
Comments
bobbymartinez726 :
I would say a 15 amp circuit would trip at 12 amps it’s a topic a friend and I talk about often I would love to know your opinion 80% overcurent prot
2022-11-04 05:08:27
1
jason_stoffel :
I’ve heard it can cause damage to motors if there isn’t enough power available. I’m not quite sure how it works but it seems plausible.
2022-11-05 05:07:54
1
thehymie :
What if it's a 15 amp circuit/ device that identifies as a 20 ?
2022-11-04 00:54:22
31
Me.Myself.She 🪳 :
My thoughts: even a normal 12a vacuum cleaner should have a 15 amp dedicated outlet. Odds are the other things running would exceed total 15 amps.
2022-11-08 14:15:18
1
Iain Nugent :
A 20 amp load should be on a 30 amp circuit. You should never ever plan your electrical installation with the bare minimum.
2022-11-04 21:32:14
1
don-dspid2404 :
Does it hurt if you put a 20 amp breaker on a 15 amp circuit?
2022-11-04 23:13:20
1
ryan :
I agree with your professional opinion and also think random fires are not cool 😅
2022-11-04 00:51:51
4
rigamorte :
Sorry but you are wrong 80 percent rule is 16 amps is Max 20 amp circuit
2022-11-09 04:45:25
3
SM :
can you explain what is involved in adding an outlet 3 ft horizontally from existing? I'm convinced it's a small project, my spouse insists it's not$
2022-11-04 15:21:11
2
FullSttopp :
Thanks Lexi. That’s very helpful. I’ll call the electrician tomorrow. 🤙
2022-11-04 00:51:30
16
user152343863797 :
Seen so many overheated circuits - total melt Down from “growers” running 3 central A/C’s and 10 1k watt grow lights on 100 amp service lol
2022-11-04 12:03:38
1
bchangn1 :
I agree with everything you said. However, lots of appliances “require” a dedicated circuit. If you held to that for each device…100’s circuits need
2022-11-08 19:30:36
1
Richie :
How do you feel about people that used 12/3 wire to catch 2 dedicated 20 amp hits??
2022-11-05 17:43:30
1
Samuel Hernandez :
i was always taught to only use 70% of breaker capacity. if it’s a 15amp appliance, run a 20amp.
2022-11-04 01:32:44
1
J :
Does a shared 15 amp circuit peak over 15 periodically or are breakers absolute?
2022-11-04 01:17:22
1
Shwnboy :
If the appliance pulls 20a it should have a 20a plug
2022-11-06 01:21:27
2
123abcde594 :
I love this girl !!!!!
2022-11-11 15:40:29
2
Devin :
I love insulation that turns to dust as ya touch it 🤣
2022-11-04 01:05:14
2
David Brian Terry :
Spot on advice!
2022-11-04 14:11:24
2
WilsonPtippyToe :
being a welder I believe it'll always be king of trades BUT I give you electricians credit wiring is a pain
2022-11-08 04:05:37
2
David :
Also Don’t upsize a breaker without upgrading the wire or you’ll have melted wire & a fire hazard.
2022-11-04 00:53:52
2
To see more videos from user @lexi_abreu, please go to the Tikwm homepage.
Other Videos
Trying out new things 🖤
7
عندما يبدع سمير دويدي في التقرير 🎶🎶 #وثائقي #تقرير #تقرير_سمير_دويدي😍 #تقرير_بين_سبورت #المانيا #البرازيل #fyp
q mal
(@,)Hyee bawafa✌️💔#plase_viral_my_video #unfrezzmyaccount,😭😭 #dear_tiktok_team_plz_grow_my_account #foyyyyyyyyyyyyyyyyyy #😘🇵🇰
Think i killed this not sure tho
About
Robot
Legal
Privacy Policy