Just curious? Why did you still read 120 on both legs at first if one side of the breaker was bad? Was it coming back up the line from the heater?
2024-02-01 04:14:19
4
pwm79 :
breakers just dont open up. obviously a issue with the hot water heater that caused it
2024-02-04 20:02:48
3
Bill Roper :
I'm a little confused. Why not check for continuity , thermostats, and elements first? 99 out of 100 times it is an element or thermostat. not being rude just asking. Thanks for sharing.
2024-02-04 15:28:45
2
Michael :
There’s no neutral buddy. 2 hots and a ground
2024-02-02 02:03:51
2
Charlie_Tx197 :
I hate those little GE breakers great for 15 and 20s but horrible for double pole breakers
2024-06-29 17:28:10
3
Alex Abba :
nice. so when it showed zero it should of read 240 correct. I have new 200 amp set up. sometimes they read zero as well on 240
2024-02-05 02:39:43
3
Alejandro Leon :
🙏🏻🫶🐐
2024-02-01 02:42:22
2
Dave :
Some electric H2O are 120 volt ex 20 gallon 1 element 1 stat
2024-02-03 02:36:07
2
Hattie Reese859 :
how much does it typically cost to fix something like this?
2024-07-15 04:52:25
0
Zamantha :
😉
2026-01-04 21:28:31
1
jse7678 :
👍😎🔥
2024-02-02 02:14:55
2
Shandy402 :
🥰
2024-12-25 23:34:08
0
ponchotok02 :
🥰🥰🥰
2025-03-22 04:23:39
0
Todd :
Imagine that using a cheap ass, GE breaker and wondering why it failed! Should’ve used square D from the start !!!
2024-02-04 21:51:11
2
Mike Biff368 :
GE breakers are garbage.
2024-02-01 16:15:05
2