@love2hvac: A TXV does not do trop suction pressure, it controls the suction superheat. By monitoring the superheated vapor it can keep the evaporator coil with the correct amount of saturated liquid mixture. Airflow first, the. feed it enough subcooled liquid, Then the TXV will maintain superheat for us! #hvac #hvacr #love2hvac #hvactech #hvactechnician #txv

love2HVAC
love2HVAC
Open In TikTok:
Region: US
Thursday 08 August 2024 16:10:49 GMT
103218
5849
147
641

Music

Download

Comments

launchedmeerkat
Chris Nelson :
Txv more like CSV…right? Constant superheat valve?! Anyone?
2024-08-14 02:18:28
4
phantomrio2
PhantomRio2 :
Not a HVAC guy . . . this went over my head after 10.5 seconds. Much respect to you guys.
2024-08-08 17:07:29
44
918.hvacr
Jesus S :
Another good topic on sub cooling is just bc you have 9 sc outside doesn’t mean you have a full column getting to the TXV.
2024-08-08 16:42:52
8
briceauger
Brice Auger :
No one explains how the sensing bulb and equalizing tube adjust the position of the needle inside the txv. Would really help tech out there understand how it’s “calculating”.
2024-08-08 16:43:35
12
trampisg
Hoss :
There is also a EPRV and a CPRV . Evaporator pressure regulating valve and crankcase pressure regulating valve!
2024-08-13 08:41:04
0
jdominican36
Miguel 🧡 🚣 :
any tip with high humidity in unit without any water leak
2024-08-13 21:53:38
1
zeala2020
Zeala2020 :
If the sc and pressure is good at the txv inlet and still high sh, txv is bad. Warming and cooling txv only tells you that it modulates, nothing more so meaningless imo. Sh/sc can be made more or less
2024-08-09 12:17:17
1
b_easy67
b_easy67 :
Got1 for u guys, fan kicks off after about a minute, but compressor still runs changed capacitor, and fan motor. Could it be a dirty a coil? Old R22 unit I know it should be changed.
2024-08-08 23:56:41
1
adam_straight
Bubka007 :
Beer can cold biscuit warm jnow what I’m saying
2024-08-09 12:01:09
0
manzanillo2010
Cuba :
I disagree
2024-08-09 18:03:25
0
finkelstein78_2.0
finkelstein78_2.0 :
BYW, high superheat and high sub cool= bad metering device.
2024-08-10 18:27:22
0
tgarthe
thegarthe :
External equalize also equalizes system on shut down
2024-08-09 01:28:29
0
nrhc.hvac
Neighbors HVAC LLC :
Where is the best spot for the sensing bulb inside the cabinet or out?
2024-08-09 00:58:49
0
tech_nasty
Tech Nasty :
Airflow? Doesn’t that mean you gotta read and do math n stuff?
2024-11-28 23:50:50
0
mud.in_my.blood
Mud in my blood :
why does one side of my evap coil get really cold and one side barely cold
2024-08-22 10:58:58
0
a_dam_king
Adamslomeli :
And what do you read on the gauges ?? Low and high side ?
2024-08-09 08:15:41
0
robredwest
red :
Very well done👌. Check your filter, check blower, then start to think about txv. Changed out a handful this summer. Please people, quit shooting uv dye+ sealant into lines. Find it and fix it.😂
2024-08-09 00:16:35
5
javi1k
jmann1297 :
Can you make a more in depth video on troubleshooting a txv and how to know 100% that the txv is faulty
2024-08-08 17:20:17
5
german.castellano24
German Castellano :
excelente y gracias por la traducción.
2024-08-10 00:39:56
1
hvac_refer_guy
HVAC_REFER_GUY®️ :
Nailed it.
2024-08-11 00:04:09
2
thewilliebeast
aaron the handyman :
as I like to say the main job of the txv is to ensure you are always getting 100% vapor back to the compressor.
2024-08-21 13:01:51
1
thehvacexperience
HvacJo :
Very informative , great job!
2024-08-30 10:27:27
1
2fingeramputee
Jay Shepherd :
Tell it man! Temperatures.😁
2024-08-12 10:52:30
1
sageman731
Sage :
I bet there’s a bunch of different pressures inside that magic valve…good job Ty, the young guys will never quit blaming them. Non adjustable for them for a reason LOL
2024-08-09 03:36:36
1
german.caicedo.p
Im_just_curious_ :
so no more "beer can cold" Ty? lol
2024-08-10 22:54:37
1
To see more videos from user @love2hvac, please go to the Tikwm homepage.

Other Videos


About