@masterspowersolutions: Today we installed a new 3 phase power circuit for Inova Air. This circuit powers one of their heavy duty sheet metal slip roll machines, designed to roll out and form metal with precision for manufacturing. We made sure it’s all done to the highest standard ✅ with RCD protection for safety and overload protection for reliability, keeping both people and equipment protected. #ElectricalSafety #Level2Electrician #SwitchboardUpgrade #IndustrialElectrician #CentralCoastElectrician
Why didn’t you install a 3phase RCBO in the switchboard? Just generally curious. The circuit is only RCD protected from the field RCD. Also, pretty sure those RCD enclosure are pretty expensive
2025-08-26 03:23:26
1
Laurence Refalo :
does that mean you just install a standard CB in the orange board
2025-08-25 21:09:43
1
Jimi Ruf :
Why have you used an CB from the Msb into an RCD instead of just using a 4pole RCBO?
2025-08-26 00:04:02
3
NickCranston :
Simple way to keep it compliant is to use a 100mA RCBO at the board and a 30mA RCBO at the isolator, this satisfies the regs and maintains discrimination clauses.