Getting the right motor is the easiest fix. You can hop on automation direct and get a small frequency drive and fix it that way as well depend depending on how much they want for the motor
2025-11-20 01:55:45
6
JB77 :
Get the right motor
2025-12-29 23:49:56
0
GODis1st :
I’m just happy I knew the word asynchronous! 🤣🤣🤣 But man did I die laughing when you said “I’m not gonna try it, I’m not gonna do it …I’m not doing it!” 💀 💀💀 Thank you for the correct start to 2026!!!
2026-01-01 07:58:30
0
tmaust84 :
208Y (3ø-n-g) panels are usually 3 phase however equipment is not always 3 phase. Same as a house your WH is (h-h-g)
2025-12-06 14:42:42
0
golfingsocal87 :
That and or a small 3 phase converter for that little guy is 115 bucks.
2025-11-20 02:00:53
5
Sig Sauer P227 :
Never heard of 208Y being single phase. Explain that to me
2025-12-04 01:55:34
0
Adonitas496 :
get a 240 single phase motor. the 240 rating is its top voltage rating, but it probably has a lower triggering and around 200 volts. The only other option is to get a converter to three-phase, which is more complicated than just getting the right motor.
2025-12-07 12:52:27
1
Wrightous :
Bro I’m confused so do u get a new motor or are u gonna make it work. 208v is a different service which I don’t see up in my area much. But when it come to 3 phase compared to single phase.. I’m confused bro on your explanation..
2025-11-20 03:56:08
0
2L8uLuz :
A -SINK-RUH -ness an induction motor and that Jerky looks yummy
2025-11-20 15:20:56
2
freddiemac51 :
Option B - buy the transformer that ups the voltage
2025-11-20 01:44:40
1
freddiemac51 :
Option A - run a 3rd phase and make some money
2025-11-20 01:44:12
2
Will :
😎😎😎
2025-11-20 02:16:07
1
danielveasey938 :
You could do a buck boost transformers to create a third leg but it would be too expensive
2025-12-30 01:54:04
1
Chris 🇨🇦 :
The panel should have never been fed with only 2 legs of the 3 phase system. Sounds like they used what was available and figured they only needed 2 phases for the single phase 240v motor. 2 phases of 208v is still 3 phase and is not the same as 240v single phase as 208 has a neutral tapped Wye. The motor would have worked for a bit but the low voltage and phase shift is likely why it died. In my opinion you need to either a) Transform to 120/240 from the 3 phase system and feed 240v single phase, replacing with the original manufacturer spec motor, or 2) pull all 3 phases into the box and use a new 3 phase motor (the one he bought is 240v delta and you have a 208v Wye feed).
2025-11-20 03:14:39
3
Al :
The motor is for a 4 wire 3p delta system but will maybe run ok on 208v 3p
2025-11-20 02:11:51
1
Lexan's Ghost🐋 :
I’m confused. You’re confused. We’re all confused kehd.😂😂😂
2025-11-20 03:17:17
1
Dave :
LMAO
2025-11-22 19:00:33
0