Needs full rebuild, piston rings, valve plates, all gaskets, use methylated spirits to clean the heads and all surfaces. Or u can swap the comp as well but thatll be $5k+
2026-06-27 10:30:44
2
CharlieO :
What cools the compressor?….. Superheat. Allow the unit to run for more than 15-20 mins and checked the returning suction line temp vs saturation.
2026-06-24 06:40:12
1
✌️ :
i don’t know bro i just started this stuff 😭
2026-06-12 01:10:13
16
Hailey💖💫 :
Are your pistons moving free when you push them in? One should move up freely when you push one down. You shouldn’t notice any cracks on the pistons either. If you have to hit it with a hammer to move the piston that’s no bueno
2026-06-13 02:24:35
0
Dro5.0. :
Make sure the comp isn’t bleeding by do a pump down test make sure suction holds valves or reeds might be broken if don’t hold
2026-06-12 02:19:53
1
akashworth :
whats that tool?
2026-06-26 18:16:50
0
mike “stay cool” g :
Call ur service manager they high key need new compressor
2026-06-12 23:05:04
0
Jeremy Graves :
Valve plate piston or something related to pumpin vapor, if the 2 other head does all the succion the third will hot ass Hell. Put your gage on succion, close that rotolock, supposed to go 20-30 inch vacuum in a second and Keep it there for long, unless you got a trouble
2026-06-14 02:48:35
0
kksay16 :
Do this 😭
2026-06-13 11:25:05
0
n8flannery :
Pump down test needed but more than likely the valve plates are cooked
copper plating on discharge valves, must have had moisture or has in system. Valve plates rooted. Looks like the gasket leaking on head or split when took apart. Quote for service exchange or replacement of compressor.
2026-06-12 14:27:56
0
Alex :
Everything getting resurfaced or replaced 😭
2026-06-12 05:21:36
0
Out of Gas | HVAC/R :
@Klein Tools
2026-06-26 20:38:22
0
To see more videos from user @outofgashvacr, please go to the Tikwm
homepage.