@realacstew: Let me know fr, I’m just chillin on this ladder right now doing some research #hvac #hvactechnician #carrier #hvaclife #trades

ACSTEW
ACSTEW
Open In TikTok:
Region: US
Saturday 20 June 2026 21:05:04 GMT
30025
1109
296
26

Music

Download

Comments

ogniram
ogniraM :
how many units do you have with same issue?
2026-08-14 13:12:55
0
gafferdude
Gafferdude :
High delta T = low flow. Those WSHPs don't like gunk in the water. and many condenser water systems are gunky.
2026-08-14 07:37:26
0
bs_bourbon_channel
BS Bourbon Channel :
Clean the strainer bro
2026-06-21 00:24:36
79
dannyjara_
DannyJara_ :
Normal condenser water delta is about 8-12. If you have a water flow issue, your water delta will be high just like what your experiencing, theirs not enough water to carry away heat. Heat is transferring well, but because your water flow is slow, it makes your return water extremely warm/hot. If you had a plugged heat exchanger, you will see much less delta, closer to about 2-5 degrees on your water because the heat isn’t being transferred due to scale build up, etc. 🤝
2026-06-21 06:29:03
35
adamdeckardbaby
Adam Deckard Baby :
Q = 500*GPM*dT
2026-06-21 11:38:40
12
bignbrown
Dario Miller :
Had the exact same thing happen with one of those units. Ended up putting a flow gauge in line so I could see the gpm and it ended up being a flow issue with the building pumps.
2026-06-21 03:15:58
14
bluecollarpresident
Legacy Air Home And Office Sol :
CLEAN THE STRAINER BRO UR WATEE IS BARELY MOVING THRU AND PICKING UP WAY TOO MUCH HEAT IF THIS IS THE OBKY UNIT DOING IT THEN ITS THE Y STRAINER RIGHT THERE IN THE VIDEO IF MULTIPLE OF THEM R DOING IT CHECK YOUR PUMP AND COOLING TOWER AND STRAINER AT THE PUMP
2026-06-21 14:53:18
5
letsbetechs
Lets Be Techs :
the flow through the unit is going to be e dependant on the pressure of your supply minus the pressure of your return. do these open and close with a solenoid or are they free flowing through every machine in the building? and if it's 3 way actuated too many upstream that have the flow too high can keep the return line pressure too high so very little flow when both hooked up, if that makes sense
2026-06-21 15:41:40
5
ozhole
ozhole :
Clean the strainer and flush unit
2026-06-21 16:27:32
8
ypfavoritedoggieboy
user146850 :
on the top water line, THE RETURN, adjust your circuit setter to around 10 psi see if that helps, definitely could be that a circulation pump is not working properly or the strainer on the circulation pump is plugged
2026-06-20 22:31:46
9
s2kddeunspr
jester :
issue is with the supply to your unit. not the unit itself. not your problem. you already did what you have to do call the management and have them fix that issue. go home.
2026-07-25 13:08:20
3
conner6776
Conner Nelson :
whats the inlet condeser water temp? and whats the refrigerant super and sub?.
2026-06-21 18:27:19
4
edwardmoore625
Eddie :
Heat exchange dirty
2026-06-23 15:03:25
4
sharkmiami
Ray :
Maybe there isn't actually any water flow; instead, you might be seeing backflow through the coils.🤝🤝🤝
2026-06-21 14:08:13
3
kerkerathletics
Kerker_Athletics :
check your strainer
2026-06-29 19:25:52
3
acechtdguvq
Ace :
Did you check the loop pump and tower, make sure the all the strainers are clean! I know in Philly I try to maintain a 80 degree loop temp
2026-06-21 09:36:49
6
tonyhvac1
tonyhvac :
Water pressure isn’t the answer, need to check pump, if you have head pressure regulator etc. etc. etc.
2026-06-23 20:01:47
2
todd_chap
Todd chap :
screen
2026-06-23 05:43:36
3
lestercanady4
lestercanady :
txv
2026-06-21 13:17:02
4
lattahead
Casey Latta :
Clean all the strainers
2026-06-21 15:12:32
4
spencerbyrum
Spencer :
clean the strainer
2026-06-21 19:02:19
4
wbee64
Miguel Diaz :
increase the speed to the condenser water pump
2026-06-21 14:34:54
4
hvacdude6
HVACDude :
No water flow
2026-06-22 14:35:57
3
greengt2013
GreenGT2013 :
How far away is the condenser water pump from the unit? Is the pump on ? You might flow from building head pressure not from the pump.
2026-06-22 02:50:19
4
brandez102
ELDADDYB :
Check the pumps VFD see what it’s set to also make sure your water inlet temp is within range, if not, you could have an issue with your tower fans
2026-06-23 22:31:02
4