High delta T = low flow. Those WSHPs don't like gunk in the water. and many condenser water systems are gunky.
2026-08-14 07:37:26
0
BS Bourbon Channel :
Clean the strainer bro
2026-06-21 00:24:36
79
DannyJara_ :
Normal condenser water delta is about 8-12. If you have a water flow issue, your water delta will be high just like what your experiencing, theirs not enough water to carry away heat. Heat is transferring well, but because your water flow is slow, it makes your return water extremely warm/hot. If you had a plugged heat exchanger, you will see much less delta, closer to about 2-5 degrees on your water because the heat isn’t being transferred due to scale build up, etc. 🤝
2026-06-21 06:29:03
35
Adam Deckard Baby :
Q = 500*GPM*dT
2026-06-21 11:38:40
12
Dario Miller :
Had the exact same thing happen with one of those units. Ended up putting a flow gauge in line so I could see the gpm and it ended up being a flow issue with the building pumps.
2026-06-21 03:15:58
14
Legacy Air Home And Office Sol :
CLEAN THE STRAINER BRO UR WATEE IS BARELY MOVING THRU AND PICKING UP WAY TOO MUCH HEAT IF THIS IS THE OBKY UNIT DOING IT THEN ITS THE Y STRAINER RIGHT THERE IN THE VIDEO IF MULTIPLE OF THEM R DOING IT CHECK YOUR PUMP AND COOLING TOWER AND STRAINER AT THE PUMP
2026-06-21 14:53:18
5
Lets Be Techs :
the flow through the unit is going to be e
dependant on the pressure of your supply minus the pressure of your return. do these open and close with a solenoid or are they free flowing through every machine in the building? and if it's 3 way actuated too many upstream that have the flow too high can keep the return line pressure too high so very little flow when both hooked up, if that makes sense
2026-06-21 15:41:40
5
ozhole :
Clean the strainer and flush unit
2026-06-21 16:27:32
8
user146850 :
on the top water line, THE RETURN, adjust your circuit setter to around 10 psi see if that helps, definitely could be that a circulation pump is not working properly or the strainer on the circulation pump is plugged
2026-06-20 22:31:46
9
jester :
issue is with the supply to your unit. not the unit itself. not your problem. you already did what you have to do call the management and have them fix that issue. go home.
2026-07-25 13:08:20
3
Conner Nelson :
whats the inlet condeser water temp? and whats the refrigerant super and sub?.
2026-06-21 18:27:19
4
Eddie :
Heat exchange dirty
2026-06-23 15:03:25
4
Ray :
Maybe there isn't actually any water flow; instead, you might be seeing backflow through the coils.🤝🤝🤝
2026-06-21 14:08:13
3
Kerker_Athletics :
check your strainer
2026-06-29 19:25:52
3
Ace :
Did you check the loop pump and tower, make sure the all the strainers are clean! I know in Philly I try to maintain a 80 degree loop temp
2026-06-21 09:36:49
6
tonyhvac :
Water pressure isn’t the answer, need to check pump, if you have head pressure regulator etc. etc. etc.
2026-06-23 20:01:47
2
Todd chap :
screen
2026-06-23 05:43:36
3
lestercanady :
txv
2026-06-21 13:17:02
4
Casey Latta :
Clean all the strainers
2026-06-21 15:12:32
4
Spencer :
clean the strainer
2026-06-21 19:02:19
4
Miguel Diaz :
increase the speed to the condenser water pump
2026-06-21 14:34:54
4
HVACDude :
No water flow
2026-06-22 14:35:57
3
GreenGT2013 :
How far away is the condenser water pump from the unit? Is the pump on ? You might flow from building head pressure not from the pump.
2026-06-22 02:50:19
4
ELDADDYB :
Check the pumps VFD see what it’s set to also make sure your water inlet temp is within range, if not, you could have an issue with your tower fans
2026-06-23 22:31:02
4