@acservicetech: Make sure that you are aware of this issue when installing condensate overflow switches! In this scenario the emergency switch may not trip if there is some sort of condensate clog and the water may flow over the pan, through the unit, and into the building structure. Also, make sure to have a pan under the unit to catch any water and make sure to seal the pan hole and mount a condensate switch in the pan. There should never be any water in the secondary pan under the unit! Enroll in our online HVAC Academy to learn about condensate safety switches https://hvaccourses.acservicetech.com/course/condensate-safety-switches Join our online HVAC Academy and gain access to 43 courses, 105 hours of training, and earn 63 certificates to learn and grow in this trade: https://www.acservicetech.com/academy . . . #condensate #switch #pitch #hvac #hvacr #overflow #water #pressure #hvactech #airflow #technician #hvactraining #acservice #acservicetech #courses #hours #certifications
That's great info. I would love to see a video with more detail on properly piping these units. We are told to use a ptrap on all our units. Especially on negative pressure systems. On ours however, we have the Tee located after the trap. We are told it will only drain if piped this way
2026-08-02 21:07:06
2
Jesse Payne🦆 :
Unit has my last name btw😂😂
2026-08-03 00:22:23
3
Qbell :
I’ve been piping all those switches low. I thought I needed too in all of them, not just the Bryant/carrier
2026-08-03 10:13:28
0
simple76 :
Negative needs a trap with a vent after the trap
2026-08-04 12:30:51
0
mikecianfrocco/hvac grapevine :
Whats up with that coil!! Need a switch on the inside pan wow
2026-08-13 13:33:12
0
Jacurb :
Genuine question with no malice. Where is the vent tee? Its a furnace positive pressure needs a vent?
2026-08-06 00:39:08
0
J :
yea get a ez-trap problem solved
2026-08-02 20:54:59
2
Ryan Foster :
inspector says it has to be there
2026-08-03 18:44:57
0
grim :
Positive pressure condensate traps are, in my opinion, important due to insect and oder issues.
2026-08-02 22:52:04
2
Jesse Payne🦆 :
That’s why I have a secondary drain switch and an in-line drain switch
2026-08-03 00:21:16
1
test--tickle :
what a Payne in the butt 😅
2026-08-03 00:52:30
0
tim :
😂😂😂
2026-08-03 07:56:11
0