iiDejay :
perfect example of why it's never just a tripped breaker, my coworker went out for first call, reset the breaker, made sure it turned on then left, then I got a call back at like 5pm to go back out and see why it's not working anymore, I reset the breaker everything fires up except I checked amp draws, pressure readings, temp split, everything, my pressures were like 160 over 540 with sh at 38 and SC at 0, pulled 4 lbs of refrigerant out cuz it was so overcharged and thought that caused the compressor to amp too high, I then took amp draws again and looked much better but then I went to test my LRA and the compressor didn't kick on and my 38 LRA kicked the 15amp breaker, come to find out my factory hard start/relay kit had failed, long story short, it's never just a tripped breaker
2026-08-16 19:26:32