@reign_tech: More reason to always protect your solar system with the right protective devices. 💯 ⚡️🛡️ Don’t wait for “Gbumu” before you protect your investment. 😂🔥⚡️ #solarinstallation #solarenergy #cleanenergy #surgeprotector #fyp
How on earth do you expect that SPD to discharge surge through that 2.5mm abi 1.5mm cable? SPD earth cable cable should be a minimum of 6mm full gage and when the distance is far, you use 16mm, not even 10mm.
2026-08-17 21:14:04
5
modernelectricalwiring :
The SPD is not designed to operate like this. Check the breaker properly because the overheating is most likely coming from the breaker or its connection. An overloaded or poorly connected breaker can generate excessive heat, which may eventually affect the SPD. So the main problem should be investigated at the breaker and its wiring, not assumed to be normal SPD operation.
2026-08-18 00:13:05
4
drola04 :
The fire extinguisher failed
2026-08-17 18:49:41
7
Edo/benin-city solar dealer, :
make una avoid 2.5mm for solar use 6 mm ac wire only
2026-08-18 20:30:00
4
FreEthinker SOLAR solutions :
Client say after phcn work finish them hear gbumoo🤣😂😂
2026-08-17 22:50:09
3
Daniel Uncovered :
SPD are not designed to work this way, this is a BAD spd and capable of of causing fire outbreak
2026-08-17 15:17:48
2
BLACKDOVVE🖤 :
There’s no breathing space between those breakers separate AC protective devices from DC !!
2026-09-06 16:26:39
0
KESSTECH SOLAR PRO.. :
this is what u get wen u use an undersized DC breaker oga..notin protect there
2026-08-28 19:50:07
0
Engr Promise U. :
U sabi work so?
2026-08-17 20:47:54
0
🍊 ÓɌÃŊƓĒ ÇÕLLÏÑṢ :
why didn't the SPD engage ? 🚨
2026-08-17 19:14:11
1
GOTROx Technologies :
The cause of this is likely to be the surge.. this type of spd is bad
2026-08-17 10:51:24
1
TiKADO ENERGY SOLUTIONS LTD :
I haven't seen any signs of earthing in your installation.
2026-08-18 03:16:29
1
Revive Tech Services :
Thank God for safety
2026-08-17 20:19:58
1
Tactician :
the so called fire extinguisher failed to deploy 😆
2026-08-17 19:16:43
0
22 AUGUST :
but Snr man abeg why u no give those breakers space to breath 😑 why jam-packed like that... 🤔 na God save u
2026-08-17 21:18:51
1
Ayorinde J. Omotayo :
same thing happened to one of my customers, they had someone fix their Nepa light and during the process the AC side SPD got burnt
2026-08-18 06:05:24
1
CRESTEDGE TECHNOLOGIES 💡🧰 :
This one go far ohh 😂😂😂
2026-08-17 08:03:57
1
Adeseye Gabriel :
This isn't a proper protection, the DC breaker should trip and not burn to this stage. The DC breaker is over sized. Recalculate your PV Amperage for the correct DC breaker to use.
2026-08-18 08:08:43
1
L£gwork :
The SPD has done its job. The surge must be really heavy
2026-08-17 19:56:02
1
GobunaTech :
A.c surge right. too Dee get that kind wahala 💯
2026-08-20 11:38:37
0
preciousdaniel34 :
true
2026-08-19 12:13:45
1
Engineer Williams 💡💡💡⚡️⚡️⚡️ :
I don’t trust this stuffs trust me
2026-08-19 21:18:11
0
Sophia Hughes :
Imagine how poor the installation is, how on earth will a technician Mage wires together instead of him to use the proper gauge
2026-08-18 14:55:52
0
Afose :
it seems there is no proper Earthing in this your connection without an external earthing connection the SPD is surely going to burn nah
2026-08-18 10:14:40
0
Tactician :
@oga solar
2026-08-17 19:18:00
0