@reign_tech: More reason to always protect your solar system with the right protective devices. 💯 ⚡️🛡️ Don’t wait for “Gbumu” before you protect your investment. 😂🔥⚡️ #solarinstallation #solarenergy #cleanenergy #surgeprotector #fyp

Reign_tech
Reign_tech
Open In TikTok:
Region: NG
Monday 17 August 2026 04:55:38 GMT
11950
357
60
48

Music

Download

Comments

engr_kelvin
Engr Kelvin :
How on earth do you expect that SPD to discharge surge through that 2.5mm abi 1.5mm cable? SPD earth cable cable should be a minimum of 6mm full gage and when the distance is far, you use 16mm, not even 10mm.
2026-08-17 21:14:04
5
modernelectricalwiring
modernelectricalwiring :
The SPD is not designed to operate like this. Check the breaker properly because the overheating is most likely coming from the breaker or its connection. An overloaded or poorly connected breaker can generate excessive heat, which may eventually affect the SPD. So the main problem should be investigated at the breaker and its wiring, not assumed to be normal SPD operation.
2026-08-18 00:13:05
4
drola04
drola04 :
The fire extinguisher failed
2026-08-17 18:49:41
7
owas.w.enterprise
Edo/benin-city solar dealer, :
make una avoid 2.5mm for solar use 6 mm ac wire only
2026-08-18 20:30:00
4
007freethinker
FreEthinker SOLAR solutions :
Client say after phcn work finish them hear gbumoo🤣😂😂
2026-08-17 22:50:09
3
daniel.uncovered
Daniel Uncovered :
SPD are not designed to work this way, this is a BAD spd and capable of of causing fire outbreak
2026-08-17 15:17:48
2
aremuolamilekan6115
BLACKDOVVE🖤 :
There’s no breathing space between those breakers separate AC protective devices from DC !!
2026-09-06 16:26:39
0
vickess13
KESSTECH SOLAR PRO.. :
this is what u get wen u use an undersized DC breaker oga..notin protect there
2026-08-28 19:50:07
0
engr_pc
Engr Promise U. :
U sabi work so?
2026-08-17 20:47:54
0
nwachinaemereife_na_orlu
🍊 ÓɌÃŊƓĒ ÇÕLLÏÑṢ :
why didn't the SPD engage ? 🚨
2026-08-17 19:14:11
1
gotrox_technologies
GOTROx Technologies :
The cause of this is likely to be the surge.. this type of spd is bad
2026-08-17 10:51:24
1
tikado.ng
TiKADO ENERGY SOLUTIONS LTD :
I haven't seen any signs of earthing in your installation.
2026-08-18 03:16:29
1
revive_tech_services
Revive Tech Services :
Thank God for safety
2026-08-17 20:19:58
1
bimbularcharles
Tactician :
the so called fire extinguisher failed to deploy 😆
2026-08-17 19:16:43
0
bobbydc993
22 AUGUST :
but Snr man abeg why u no give those breakers space to breath 😑 why jam-packed like that... 🤔 na God save u
2026-08-17 21:18:51
1
_stayjiiggy
Ayorinde J. Omotayo :
same thing happened to one of my customers, they had someone fix their Nepa light and during the process the AC side SPD got burnt
2026-08-18 06:05:24
1
crestedge.tech
CRESTEDGE TECHNOLOGIES 💡🧰 :
This one go far ohh 😂😂😂
2026-08-17 08:03:57
1
seyesworld
Adeseye Gabriel :
This isn't a proper protection, the DC breaker should trip and not burn to this stage. The DC breaker is over sized. Recalculate your PV Amperage for the correct DC breaker to use.
2026-08-18 08:08:43
1
legwork94
L£gwork :
The SPD has done its job. The surge must be really heavy
2026-08-17 19:56:02
1
gobunatech
GobunaTech :
A.c surge right. too Dee get that kind wahala 💯
2026-08-20 11:38:37
0
preciousstewart06
preciousdaniel34 :
true
2026-08-19 12:13:45
1
engineerwilliams22
Engineer Williams 💡💡💡⚡️⚡️⚡️ :
I don’t trust this stuffs trust me
2026-08-19 21:18:11
0
sophy20174
Sophia Hughes :
Imagine how poor the installation is, how on earth will a technician Mage wires together instead of him to use the proper gauge
2026-08-18 14:55:52
0
afoseco
Afose :
it seems there is no proper Earthing in this your connection without an external earthing connection the SPD is surely going to burn nah
2026-08-18 10:14:40
0