@wyxelware: Stop dumping gas into systems just because the sight glass is bubbling! 🛑 Bubbles indicate flash gas—not automatically a low charge. Before reaching for the tank, check: 1️⃣ Restricted filter drier (look for a temperature drop across it) 2️⃣ Excessive vertical pipe lift 3️⃣ TXV hunting during load shifts Charge by subcooling and superheat—never by the glass. 🛠️ #HVAC #HVACTech #HVACLife #Refrigeration #ApprenticeTech
That's why you charge according to subcooling and check superheat then you can't go wrong
2026-09-05 17:53:33
5
Sammy :
Check expansion valve needle position first
2026-09-06 14:32:59
1
sounds good 2 me :
More gas always 👍
2026-09-06 17:40:07
0
turbo :
Not necessarily that means you are undercharge possible a leak somewhere
2026-09-04 23:38:50
1
drphill'sdad :
no reasonable explanation for vapor in the liquid line when running. now, a clear glass doesn't necessarily mean its full either.....flooded head pressure control etc.....
2026-09-04 21:12:06
4
thegarthe :
Video cut off
2026-09-05 12:58:31
0
junior58692 :
ok?????
2026-09-04 20:46:47
0
mooch 1 :
Yup
2026-09-04 22:54:05
1
Rob Middleton20 :
it is never a final problem ! it's a piece of information and how you use it is bloody important . but some of us know that
2026-09-04 23:54:29
2
Wyxelware. :
Wyxelware.com!!!!!
2026-09-06 15:02:05
0
imad dannun :
😁😁😁
2026-09-05 12:21:42
0
ألــــبـــــرنــس لـــتـــبريد :
👍
2026-09-05 12:11:20
0
mersalin :
👍
2026-09-05 17:31:03
0
To see more videos from user @wyxelware, please go to the Tikwm
homepage.