@wyxelware: Stop dumping gas into systems just because the sight glass is bubbling! 🛑 ​Bubbles indicate flash gas—not automatically a low charge. Before reaching for the tank, check: ​1️⃣ Restricted filter drier (look for a temperature drop across it) 2️⃣ Excessive vertical pipe lift 3️⃣ TXV hunting during load shifts ​Charge by subcooling and superheat—never by the glass. 🛠️ ​#HVAC #HVACTech #HVACLife #Refrigeration #ApprenticeTech

Wyxelware.
Wyxelware.
Open In TikTok:
Region: US
Friday 04 September 2026 16:09:21 GMT
20732
424
18
12

Music

Download

Comments

teemaster440ml
thabza 12 :
air enemy of any refrigerator
2026-09-06 19:11:47
0
unknown2smooth
Lee :
Explain why sir
2026-09-04 19:18:55
7
jacques.la.gange
jacques la gange :
That's why you charge according to subcooling and check superheat then you can't go wrong
2026-09-05 17:53:33
5
sa_neo1
Sammy :
Check expansion valve needle position first
2026-09-06 14:32:59
1
soundsgood2me2
sounds good 2 me :
More gas always 👍
2026-09-06 17:40:07
0
turbo9321
turbo :
Not necessarily that means you are undercharge possible a leak somewhere
2026-09-04 23:38:50
1
drphillsdad82
drphill'sdad :
no reasonable explanation for vapor in the liquid line when running. now, a clear glass doesn't necessarily mean its full either.....flooded head pressure control etc.....
2026-09-04 21:12:06
4
tgarthe
thegarthe :
Video cut off
2026-09-05 12:58:31
0
junior58692
junior58692 :
ok?????
2026-09-04 20:46:47
0
mooch136
mooch 1 :
Yup
2026-09-04 22:54:05
1
robmiddleton5
Rob Middleton20 :
it is never a final problem ! it's a piece of information and how you use it is bloody important . but some of us know that
2026-09-04 23:54:29
2
wyxelware
Wyxelware. :
Wyxelware.com!!!!!
2026-09-06 15:02:05
0
imad.dannun
imad dannun :
😁😁😁
2026-09-05 12:21:42
0
user9915475712466
ألــــبـــــرنــس لـــتـــبريد :
👍
2026-09-05 12:11:20
0
priyanthamersalin
mersalin :
👍
2026-09-05 17:31:03
0
To see more videos from user @wyxelware, please go to the Tikwm homepage.

Other Videos


About