@sydney_hvac: We carried out an initial fire test at a new site we’ve picked up and identified some issues with the motorised dampers not closing. The wiring looks to have been added as an afterthought, as the relays that were added weren’t shown on the wiring schematic. If the AHU was set to manual on the mechanical board, the dampers weren’t closing once the duct probe was activated. A small change to the wiring was made, and everything is now operating as intended. #hvac #repair #hvacrepair #electrical #fire
Illegal control there. FFCP is required to bypass the drives safety to run to destruction and BMS speed should be electrically interlocked with the start signal from FFCP to be unable to provide a speed ref to the drive. Crazy some of this stuff gets signed off
2026-09-06 09:11:22
0
To see more videos from user @sydney_hvac, please go to the Tikwm
homepage.