@sydney_hvac: We carried out an initial fire test at a new site we’ve picked up and identified some issues with the motorised dampers not closing. The wiring looks to have been added as an afterthought, as the relays that were added weren’t shown on the wiring schematic. If the AHU was set to manual on the mechanical board, the dampers weren’t closing once the duct probe was activated. A small change to the wiring was made, and everything is now operating as intended. #hvac #repair #hvacrepair #electrical #fire

sydney_hvac
sydney_hvac
Open In TikTok:
Region: AU
Sunday 06 September 2026 08:26:57 GMT
4137
125
1
8

Music

Download

Comments

poopeeeeeeeeee2
Poopoopeepee :
Illegal control there. FFCP is required to bypass the drives safety to run to destruction and BMS speed should be electrically interlocked with the start signal from FFCP to be unable to provide a speed ref to the drive. Crazy some of this stuff gets signed off