Need ev charger outlet and replace the romex with proper size as you have #8 romex and should be #6 romex
2026-10-03 16:25:16
32
DGibson :
Must be a EV outlet.
2026-10-03 16:22:42
11
MSlade :
Hardwire these. No outlet needed. Also needs to be GFCI breaker.
2026-11-27 01:31:40
0
Insane in da Membrane :
You were ready to blame the previous guy
2026-11-27 01:09:01
0
Oblong Johnson :
40a breaker in a 48a continuous load?
2026-11-27 00:18:23
0
robertsteich3 :
Call that customer back. Have him unplug it from the car, then the wall. Finally reseat the adapter as it had come out somewhat. As the circle part below is not flushed. Also look into having a cradle of sorts for the mobile connector so it’s hanging from that instead of the adaptor.
2026-10-04 18:49:33
19
chuckpoole836 :
40a is undersized, shouldn’t it be a 60a
2026-10-04 14:29:54
12
Dustin Ferrare :
40amp breaker is wrong. Should be 50. Also needs to be GFCI
2026-10-05 23:04:49
5
Fromthesoil :
Undersized wire and non EV rated outlet
2026-10-05 00:32:15
13
Republic Guerrilla :
thats not rated to be an EV charger outlet. they should have the car charger symbol on them its usually green.
2026-11-05 06:08:43
5
Rzr64 :
Has to be sized for Continuous Load....125 percent
2026-10-03 22:41:47
17
CK :
Problem was it’s not an EV rated outlet.
2026-10-05 21:25:03
3
Bob A Buoy :
They got the receptacle discoloration because a standard 2P 50A is not rated for a continuous load. The EV rated 2P 50A is made with a high temp plastic & Internals rated for a continuous load
2026-10-03 19:03:56
8
Susanna M. :
Would love an update…
2026-10-04 18:47:44
3
Richard Pedroza :
When you feel heat in a plug what causes it? anyone
2026-11-23 08:40:00
0
WorthEveryDollar :
Usually the Amps are pre set in the Tesla to 48 amps. You have to change that setting in the car to pull less amps if you want to use a mobile charger. Could be causing the over heating
2026-10-05 03:36:06
0
Jason :
You could manually adjust the charging amperage, charging will be slower but won't overheat.
2026-10-05 17:23:51
2
Pervernoned :
I get a similar message occasionally with my wall charger and it’s not hot and the wires and breaker are sized properly. If I cycle the breaker it works fine.
2026-10-22 12:16:50
1
Scott Betz :
put clamp meter on and see what its really pulling
2026-10-19 22:59:13
1
Brian Djordjevic :
On the Tesla you have to put the max charging at 40 amps they could have it at 50 or more.
2026-10-03 18:26:31
1
Shane Howell :
Idk can’t tell but when I installed them got to be number 6 wire and we put them on a 60 amp breaker
2026-10-03 17:53:25
0
Wayne :
Didn’t use a gfi breaker. Thats a No No….
2026-10-04 01:08:08
1
EVengineer :
This is why a hardwired charger will always be superior
2026-10-06 10:43:44
1
michael523a :
Bro, if you don’t know by just looking at that outlet, it’s the wrong outlet. It’s a range outlet. This has been going on for the last couple years anybody that’s a true Electrician knows you use an outlet that’s EV rated for a Hubble.
2026-10-06 02:44:01
1
Ted Terry :
Was it a hot day. I had to turn down my amperage charging the car. No more issues
2026-10-11 10:50:59
1