@hendythesparky: POV: An Electrician Installing a Home EV Charger for $2,790.00, 125 FT Wire Run; What an Entire Job looks like Start to Finish, Thoughts? #electrician #bluecollar #electricalcontractor #hendythesparky #trending
what’s the point of offset??? just continue the 90🤨
2026-10-21 00:18:06
168
xxi :
POV Tesla hard wired is rated for 48 amps of continuous load, therefore you have to size it at 125% which would be 60amps continuous load. 6/2 nmb is setting your customer up for failure. No max performance
2026-10-21 05:25:01
10
smkelectrical :
My local inspector wants us running copper 6/2 SEU or MC for a car charger because you need to multiply your 48a EV at 125%. 6/2 NM isn’t rated for 60a.
2026-10-21 19:48:12
0
bcunningham2021 :
im just here for all the comments
2026-10-21 00:11:56
23
prodpsilo :
What was the point of the offset above the charger? Just curious as to why the offset was needed
2026-10-21 00:12:34
8
SRT_Solis_392 :
Straight rat work… straps every 3 feet are you serious?
2026-10-22 20:33:52
4
Shadow :
Does that price include the actual charger unit?
2026-10-21 11:20:22
1
king roy :
GFCI breaker.
2026-10-21 01:37:40
2
Drew :
Why not run 4AWG so if they upgrade their charger to the level 2, they’re set
2026-10-21 00:12:17
12
Iggman51 :
Rip off no doubt.
2026-10-21 01:45:16
1
Andre :
That length is over 50ft the wire size is under size for that continuous load ! Cannot get max output from charger. Yuh raw deal that customer
2026-10-21 09:54:53
4
PengoAsteroid :
Should have ran 6/2 MC cable all the way from panel to charger. Cheaper faster better amperage up to 60 amps.
2026-10-22 09:52:56
3
Kayden_bunten :
That charger pulls 48 amps. Unless you had the client set the amperage of the charger lower I don’t think 6 awg nmb is rated for the 48 amp continuous load
2026-10-21 04:03:16
3
bobbyf628 :
we normally put those on GFI breakers
2026-10-21 02:40:27
0
Jacob :
Holy strapping
2026-10-22 03:02:01
7
Craig MCA Haskins :
As an electrician I can honestly say that price is criminal...!!!
2026-10-21 15:57:02
5
Puertombian :
I ran my own and all the conduit is hidden , no ceiling conduit showing , electricians take the easy way out and install 100ft of conduit all over the ceiling
2026-10-21 02:53:44
0
PengoAsteroid :
Where’s your means of disconnect?
2026-10-22 09:53:50
0
Christopher Shay :
Electric chargers need to be in a raceway
2026-10-21 03:17:26
1
Hazzmatt__400 :
60 amps
2026-10-21 04:00:23
1
misaelramirez766 :
2026-10-23 00:08:19
1
Kyle Warren :
I was going to say something about overcharging until I saw how long that basement was. bro could have definitely replaced that piece of conduit though and not had that offset after that 90 that just makes it ugly in the customer's garage my man
2026-10-21 01:41:25
3
Steeler_In_Leafs_Land :
As an ‘electrician’ with 5 years experience - does that mean you been licensed for 5 years OR that you are a 5th year apprentice ?
2026-10-22 02:39:55
1
Kgt :
Volt drop enters the chat 😂
2026-10-21 01:07:24
2